Recirculating Cooler

71

Command

Parameter

Response of recirculating cooler

in_par_11

none

Tn control parameter of the cascade controller.

in_par_12

none

Tv control parameter of the cascade controller.

in_par_13

none

Adjusted maximum internal temperature of the cascade
controller.

in_par_14

none

Adjusted minimum internal temperature of the cascade
controller.

in_par_15

none

Band limit (upper)

in_par_16

none

Band limit (lower)

in_mode_01 none

Selected

setpoint:

0 = SETP 1
1 = SETP 2
2 = SETP 3
3 = Last setpoint setting was carried out
through an external programmer

in_mode_02 none

Selftuning

type:

0 = Selftuning „OFF“
1 = Selftuning „ONCE“
2 = Selftuning „ALWAYS“

in_mode_03

none

Type of the external programmer input:
0 = Voltage 0 V to 10 V

1 = Current 0 mA to 20 mA

in_mode_04 none

Internal/external temperature control:

0 = Temperature control with internal sensor.

1 = Temperature control with external Pt100 sensor.

in_mode_05 none

Recirculating cooler in Stop/Start condition:

0 = Stop

1 = Start

in_mode_08 none

Adjusted control dynamics

0 = aperiodic

1 = standard

in_hil_00

none

Max. cooling power (%).

in_hil_01

none

Max. heating power (%).