Cooling water connection – JULABO SC 10000w Professional Series Recirculating Coolers User Manual
Page 15
Recirculating Cooler
15
2.5. Cooling
water
connection
Cooling water pressure (IN/OUT)
max.
6 bar
Pressure difference (IN - OUT)
3.5 to 6 bar
Cooling water temperature
< 20 °C
Notice:
Cooling water circuit
Risk of oil leaking from the refrigeration system (compressor) of the recirculating
cooler into the cooling water in case of a fault in the cooling water circuit!
Observe the laws and regulations of the water distribution company valid in the location where
the unit is operated.
Notice:
Danger of corrosion of heat exchanger due to unsuitable quality of cooling
water.
Due to its high content of lime, hard water is not suitable for cooling and causes
scale in the heat exchanger.
Ferrous water or water containing ferrous particles will cause formation of rust
even in heat exchangers made of stainless steel.
Chlorinated water will cause pitting corrosion in heat exchangers made of
stainless steel.
Due to their corrosive characteristics, distilled water and deionized water are
unsuitable and will cause corrosion of the bath.
Due to its corrosive characteristics, sea water is not suitable.
Due to its microbiological (bacterial) components, which settle in the heat
exchanger, untreated and unpurified river water and water from cooling towers is
unsuitable.
Avoid particulate matter in cooling water.
Avoid putrid water.
Recommended quality of cooling water:
pH
7.5 to 9.0
Sulfate [SO4 2- ]
< 100 ppm
Hydrocarbonate [HCO 3-]/sulfate [SO4 2-]
> 1 ppm
Hardness [Ca 2+, Mg 2+]/[HCO 3-]
> 0.5
dH
Alkalinity
60 ppm < [HCO 3-] < 300 ppm
Conductivity <
500
μS/cm
Chloride (Cl -)
< 50 ppm
Phosphate (PO4 3-)
< 2 ppm
Ammonia (NH3)
< 0.5 ppm
Free chlorine
< 0.5 ppm
Trivalent iron ions (Fe 3+)
< 0.5 ppm
Manganese ions (Mn 2+)
< 0.05 ppm
Carbon dioxide (CO2)
< 10 ppm
Hydrogen sulfide (H2S)
< 50 ppm
Content of oxygen
< 0.1 ppm
Algae growth
impermissible
Suspended solids
impermissible