Menu functions

38

Setting range: 0 ... 999

Lead time >Tv< (Differential component)

The differential component reduces the control settling time. An
insufficient lead time will prolong the time required to compensate for
disturbance effects and cause high overshooting during run-up. An
excessive lead time could cause instabilities (oscillations) to occur.

1.

Press the

button until the desired submenu is displayed -

XP INT, TN INT, TV INT.

2.

Set value:

Use the cursor keys to move left or right on the display until
the numeral you wish to change blinks.

Use the increase/decrease arrows

to change the selected

numeral (-, 0, 1, 2, 3, ... 9).

3.

Press enter

to store the value.

Continue: Press

/

or

Optimization instructions for the PID control parameters:

optimum setting

°C

t


The heat-up curve reveals inappropriate control
settings.

Inappropriate settings may produce the following heat-up curves:

Xp too low

°C

t

Tv/Tn too low

°C

t

Xp too high or Tv too high

°C

t

Tv/Tn too high or Xp too high

°C

t