Condition Monitoring Unit CMU 1000

Page 115

Revised 17.12.2009

HYDAC ELECTRONIC GMBH Mat.-No.:

669749

8.4.3 Invalid Digital Output

The quantity of digital outputs is device-dependent. This error is set when an output
terminal is selected that a device doesn't have.
► Check the selection and correct it.

8.4.4 Duplicate Digital Ouput

The output terminal of the digital output may not be present more than once in a CM
program.
► Check the adjusted output terminal and correct it.

8.4.5 Invalid Analog Output

The quantity of analog outputs is device-dependent. This error is set when an output
is selected that a device doesn't have.
► Check the selection and correct it.

8.4.6 Duplicate Analog Output

The set output of the analog output may not be present more than once in a CM
program.
► Check the output settings and correct them.

8.4.7 Too Many Boolean Output Fields

The number of Boolean output fields in one CM program is device-dependent.
► Reduce the Boolean output fields to the device-specific maximum.

8.4.8 Duplicate Boolean Output Field

The inscription of a Boolean output field may not be present more than once in a CM
program.
► Check the inscription and correct it.

8.4.9 The Bit Number Must Be a Figure between 0 and 14

The property "Bit number" may not lie outside the range of 0 ... 14 for the Boolean
output field function.
► Check the value that was entered and correct it.

8.4.10 Too Many Numerical Output Fields

The number of numerical output fields in one CM program is device-dependent.
► Reduce the numerical output fields to the device-specific maximum.

8.4.11 Duplicate Numerical Output Field

The inscription of a numerical output field may not be present more than once in a
CM program.
► Check the inscription and correct it.