Condition Monitoring Unit CMU 1000

Page 110

Revised 17.12.2009

HYDAC ELECTRONIC GMBH Mat.-No.:

669749

7.10.5 Compiling a Log Entry

The Compile log entry function is used for saving the currently
publicized values in the ongoing log recording (see Chap. 7.9.1.
Numerical output value and 7.9.2 Boolean output value).

The log entry is generated every time the input value changes from
"0" to "1".

Inputs: x:

(Boolean)

Outputs: -
Parameters: -


7.10.6 Compiling Quick Log Entries

The Quick log entries function is used for rapidly saving the currently
publicized values in the ongoing log recording (see Chap. 7.9.1.
Numerical output value and 7.9.2 Boolean output value).
Log entries will be generated at the specified time interval (p2) for as
long as the input is set to "1".
The Interim period parameter specifies that for every time stamp of a
log entry, the precise time value of the log entry will also be saved in
ms.

The log entry is generated every time the input value changes from
"0" to "1".

Inputs: x:

(Boolean)

Outputs: -
Parameters:

p1:

Interim period (Boolean)

p2:

Time in seconds


7.10.7 Start new log

Using the Start new log function, a new time-dependent or cycle-
dependent log file can be generated. The numbering in the file name
is increased by 1.
The previous log file is stored in the internal memory.

Eingänge: x: (Boolesch)
Ausgänge: -
Parameter: -


7.10.8 Transition (see Chap. 7.2.12)