beautypg.com

Bit field coding for devices which are present – EUCHNER AS-i Safety Monitor for 2 AS-i circuits User Manual

Page 87

background image

AS-i Safety Monitor for 2 AS-i circuits

Diagnostics for AS-i Monitor and networking using AS-i Master

Subject to reasonable modifications due to technical advances

Id.-No.: 103336

Issue date - 24.10.2008

EUCHNER GmbH + Co. KG

87

Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen

Tel. +49/711/75 97-0 • Fax. +49/711/753316

Bit field coding for devices which are present:

The numbers indicate the position of the bit for the corresponding device.

0:

Device is not present

1:

Device is present

11.4.3.4

Vendor Specific Object 9 - Device Colors at switch off OSSD 1

Read only.

This object contains the colors for all devices as well as additional information for
all release circuits at the time of the last switch-off of Release Circuit 1. Also sent
is which devices belong to Release Circuit 1. The information is retrieved using
the command "Get Device Colors at switch off" from the safety unit.

Byte

2

7

2

6

2

5

2

4

2

3

2

2

2

1

2

0

1

7

6

5

4

3

2

1

0

2

15

14

13

12

11

10

9

8

32

255

254

253

252

251

250

249

248

Tab. 11-18.

Coding for the states and colors

Byte

Meaning

1

Bit 0 0=Configuration mode, 1=protecting mode
Bit 3 ... 1 reserved, 0
Bit 4 status 1.Y1, EDM1 (0=open)
Bit 5 status 1.Y2, Start1 (0=open)
Bit 6 status 2.Y1, EDM2 (0=open)
Bit 7 status 2.Y2, Start2 (0=open)

2

Relay status, Output 1+2
Bit 3 ... 0 State Output 1, diag_pc.ossd[0].relay-state
Bit 7 ... 4 State Output 2, diag_pc.ossd[1].relay-state

3 ... 8

...

9

Relay status, Output 15+16
Bit 3 ... 0 State Output 15, diag_pc.ossd[14].relay-state
Bit 7 ... 4 State Output 16, diag_pc.ossd[15].relay-state

10

Bit field for devices which are present. Device 7 ... 0

11 ... 40

...

41

Bit field for devices which are present. Device 248 ... 255

42

Bit field for devices which changed in the last step. Device 7 ... 0

Tab. 11-19.