2 as-i bus connection, 3 information about the device types, 4 as-i and power supply terminal assignments – EUCHNER AS-i Safety Monitor for 2 AS-i circuits User Manual
Page 31: As-i bus connection, Information about the device types, As-i and power supply terminal assignments
AS-i Safety Monitor for 2 AS-i circuits
Electrical connection
Subject to reasonable modifications due to technical advances
Id.-No.: 103336
Issue date - 24.10.2008
EUCHNER GmbH + Co. KG
31
Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen
Tel. +49/711/75 97-0 • Fax. +49/711/753316
7.2
AS-i bus connection
7.3
Information about the device types
7.4
AS-i and power supply terminal assignments
Yellow ASi ribbon cable
Blue
AS-i-
Brown
AS-i+
2-conductor AS-i round cable
(Recommended: flexible power cable
H05VV-F2x1,5 per DIN VDE 0281)
Blau
AS-i-
Braun
AS-i+
Information!
Electrical work is to be performed only by electrical technicians.
Information!
A listing of the individual devices and their features can be found in section
Information!
The cable indicated by hatching must not have slaves or repeaters connected to
it.
The yellow cable must not have AS-i power suppliers or additional masters con-
nected to it.
Information!
The function ground should be made with as short a cable as possible to ensure good
EMC characteristics.
Attention!
The AS-I power supply for the AS-I components must have isolation per IEC 60
742 and be able to handle momentary power interruptions of up to 20 ms. The
power supply for the 24 V supply must also have isolation per IEC 60 742 and be
able to handle momentary power interruptions of up to 20 ms. The maximum out-
put voltage of the power supply must also be less than 42 V in case of a fault.