Installation, 1 dimensions, 2 connections – EUCHNER AS-i Safety Monitor for 2 AS-i circuits User Manual
Page 19: Dimensions, Connections
AS-i Safety Monitor for 2 AS-i circuits
Installation
Subject to reasonable modifications due to technical advances
Id.-No.: 103336
Issue date - 24.10.2008
EUCHNER GmbH + Co. KG
19
Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen
Tel. +49/711/75 97-0 • Fax. +49/711/753316
5.
Installation
5.1
Dimensions
5.2
Connections
Warning!
Cover the top of the AS-I Safety Monitor when doing any drilling work above the unit.
No particles, especially metal chips, should be allowed to enter the housing, since this
could cause a short circuit.
Information!
For additional information, please refer to
5 ... 6 mm / PZ2
0,8 Nm
7
LB.IN
2 x (0,5 .... 1,5) mm
2
2 x (0,5 .... 1,5) mm
2
AWG
2 x 24 ...12
10
10
Attention!
The AS-I power supply for the AS-I components must have isolation per IEC 60
742 and be able to handle momentary power interruptions of up to 20 ms. The
power supply for the 24 V supply must also have isolation per IEC 60 742 and be
able to handle momentary power interruptions of up to 20 ms. The maximum out-
put voltage of the power supply must also be less than 42 V in case of a fault.