Installation, 1 dimensions, 2 connections – EUCHNER AS-i Safety Monitor for 2 AS-i circuits User Manual

Page 19: Dimensions, Connections

background image

AS-i Safety Monitor for 2 AS-i circuits

Installation

Subject to reasonable modifications due to technical advances

Id.-No.: 103336

Issue date - 24.10.2008

EUCHNER GmbH + Co. KG

19

Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen

Tel. +49/711/75 97-0 • Fax. +49/711/753316

5.

Installation

5.1

Dimensions

5.2

Connections

Warning!

Cover the top of the AS-I Safety Monitor when doing any drilling work above the unit.
No particles, especially metal chips, should be allowed to enter the housing, since this
could cause a short circuit.

Information!

For additional information, please refer to

.

5 ... 6 mm / PZ2

0,8 Nm

7

LB.IN

2 x (0,5 .... 1,5) mm

2

2 x (0,5 .... 1,5) mm

2

AWG

2 x 24 ...12

10

10

Attention!

The AS-I power supply for the AS-I components must have isolation per IEC 60
742 and be able to handle momentary power interruptions of up to 20 ms. The
power supply for the 24 V supply must also have isolation per IEC 60 742 and be
able to handle momentary power interruptions of up to 20 ms. The maximum out-
put voltage of the power supply must also be less than 42 V in case of a fault.