The safety code sequences are replaced by the following values:
Both channels are in the safe state: 0000bin
Channel 1 is in the safe state: 0011bin
Channel 2 is in the safe state: 1100bin
No channel is in the safe state: 1111bin
NO SUBSTITUTE
The safety code sequences are transmitted via the input data.
9.6
DIAGNOSTICS
Main menu || DIAGNOSIS ||
This menu contains the following sub-menus:
For additional information refer to chap.
SAFETY SLAVES
INT MONITOR
EXT MONITOR
FAULT DETECTOR
DELTA LIST
LCS
ERROR COUNTERS
LPF
FLAGS
ACTUAL CONFIG
AS-I MASTER
SAFETY SLAVES: Safety input slaves
INT MONITOR: Display the diagnosis data for the integrated Safety Monitor
EXT MONITOR: Display the diagnosis data for the external Safety Monitors
FAULT DETECTOR: Informations about the AS-i Fault Detector
DELTA LIST: List of AS-i slaves with configuration error
LCS: List of slaves having caused a configuration error
ERROR COUNTERS: Fault counter for each single AS-i slave
LPF: List of Peripheral Faults
FLAGS: Display of the EC-Flags
ACTUAL CONFIG: Display of the current configuration
AS-I MASTER: Display of the software states