Tel. +49/711/75 97-0 • Fax. +49/711/753316
AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor
Operation in advanced display mod
9.6.11
ACTUAL CONFIG (actual slave configuration)
Main menu || DIAGNOSE || ACTUAL CONFIG ||
This function displays the status of the actual configuration of the individual AS-i
slaves.
A help appears at the end of the list explaining the abbreviations:
After selecting the desired AS-i slave address, the values for the current configu-
ration data are displayed after the respective address in the following order:
IO (I/O-Configuration) ID (ID-Configuration) xID1 (extended ID1) xID2 (extended
ID2).
ACTUAL CONFIG
0A | 1A-C
....
30A-X | 31A-D
| 1B-X
....
30A | 31B-F
HELP:
X O.K.
D DETECTED ONLY
UNKNOWN SLAVE
P PROJ. ONLY
MISSING SLAVE
C TYPE CONFLICT
F PERIPH. FAULT
A DUPLICATE ADDR
X (O.K.): The configuration data for the detected AS-i slave agree with
the designed in configuration data.
D (Detected Only): An AS-i slave is detected at this address, but it was not
designed in.
P (Projected Only): An AS-i slave was designed in at this address, but it was not
detected.
C (Type Conflict): The configuration data for the detected AS-i slave do not
agree with the designed in configuration data. The actual exist-
ing configuration of the connected AS-i slave is displayed.
F (Periph. Fault): The AS-i slave has a peripheral error.
A (Duplicate Adr.): Two AS-i slaves at the indicated address.