Spezifications, 1 technical data, 1 data sheet 103373 – EUCHNER AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor for 2 AS-i circuits User Manual
Page 18: Technical data, Data sheet 103373
18
Subject to reasonable modifications due to technical advances
Id.-No.: 103329
Issue date - 24.10.2008
EUCHNER GmbH + Co. KG
Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen
Tel. +49/711/75 97-0 • Fax. +49/711/753316
AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor
Spezifications
4.
Spezifications
4.1
Technical data
4.1.1
Data sheet 103373
Attention!
The AS-I power supply for the AS-I components must have isolation per IEC 60
742 and be able to handle momentary power interruptions of up to 20 ms. The
power supply for the 24 V supply must also have isolation per IEC 60 742 and be
able to handle momentary power interruptions of up to 20 ms. The maximum out-
put voltage of the power supply must also be less than 42 V in case of a fault.
103373
PROFIBUS interface
according to DIN 19 245, part 3
Baud rates
9,6 kBaud up to 12000 kBaud, automatic recognition
DP functions
imaging of the AS-i slaves as I/O data of the PROFIBUS
complete diagnosis and configuration via the PROFIBUS DP
Serial interface
RS 232
AS-i cycle time
150
Ps
*
(number of slaves + 2)
Safety monitor
Release circuit
4-channel
Start delay
< 10 s
Respond delay
< 40 ms
Inputs:
4 x EDM/Start
EDM: inputs of external device monitoring circuits
Start: Start inputs
switching current statical 4 mA at 24 V, dynamic 30 mA at 24 V (T=100 µs)
Output:
4 x output switching elements
relay outputs (output circuits 1 and 2)
max. contact load: 3 A AC-15 at 30 V, 3 A DC-13 at 30 V
semiconductor outputs (output circuits 3 and 4)
max. contact load: 0,5 A DC-13 at 30 V
Card slot
chip card for storage of configuration data
Displays
LCD
indication of slave addresses and error messages
LED power
power on
LED PROFIBUS
PROFIBUS master recognized
LED config error
configuration error
LED U AS-i
AS-i voltage OK
LED AS-i active
AS-i normal operation active
LED prg enable
automatic addresses programming enabled
LED prj mode
configuration mode active
LED AUX
auxiliary power