1 as-i circuit, 2 operation mode, As-i circuit – EUCHNER AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor for 2 AS-i circuits User Manual
Page 109: Operation mode, Store actual configuration store
AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor
Operation in advanced display mod
Subject to reasonable modifications due to technical advances
Id.-No.: 103329
Issue date - 24.10.2008
EUCHNER GmbH + Co. KG
109
Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen
Tel. +49/711/75 97-0 • Fax. +49/711/753316
9.9.1
AS-I CIRCUIT
Main menu || SETUP ||
To start this setup menu, an AS-i circuit must first be selected using the arrow and
the OK buttons.
The function is only available for AS-i masters with two AS-i circuits.
9.9.2
OPERATION MODE
Main menu || SETUP || OPERATION MODE ||
This function shows the current operation mode of the AS-i master:
The operation mode can be changed with "Change".
Parameters and configuration data can be modified in configuration mode, only.
9.9.3
STORE ACTUAL (store currently detected configuration)
Main menu || SETUP || STORE ACTUAL||
This function can only be executed in configuration mode.
This function enables currently detected slaves on the selected AS-i network to
be stored in the configuration of the AS-i Master.
If "Store" was successful, the LED "Config error" is turned off. The configuration is
stored and the configuration error has been eliminated.
However, if one of the connected slaves exhibits a peripheral fault, the LED "Con-
fig error" will flash.
If the AS-i master is in protected mode, the error message "Failed No Config
Mode" will appear:
Address 0 is not a permitted operation address for a slave. If an AS-i slave with
this address exists, storing the configuration will still be confirmed with "OK".
However, the configuration error remains.
AS-I CIRCUIT 1
AS-i CIRCUIT 2
OPERATION MODE
CONFIG MODE
CHANGE
PROTECTED MODE: protected operating mode
CONFIG MODE: configuration mode
STORE ACTUAL
CONFIGURATION
STORE