3 i/o data, I/o data, Process data – EUCHNER AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor for 2 AS-i circuits User Manual
Page 125
AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor
PROFIBUS DP
Subject to reasonable modifications due to technical advances
Id.-No.: 103329
Issue date - 24.10.2008
EUCHNER GmbH + Co. KG
125
Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen
Tel. +49/711/75 97-0 • Fax. +49/711/753316
11.1.3
I/O Data
11.1.3.1
Process data
Process data is arranged the same as for the Siemens and AS-i/InterBus mas-
ters. Therefore, data for slaves with a higher address are transmitted in a least
significant nibble. Additionally, the EC-flags or hi-flags, respectively, are placed
at the data location of AS-i slave 0.
2.Modul parameter erquired
Length
1
description
2 byte I
flags and AS-i detector
Tab. 11-17.
1.Possible for 2 circuits
Length
description
2 byte I / 1 byte O
safety control / status
Tab. 11-18.
Byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
0
Flags
Slave 1/1A
F3
F2
F1
F0
D3
D2
D1
D0
1
Slave 2/2A
Slave 3/3A
2
Slave 4/4A
Slave 5/5A
3
Slave 6/6A
Slave 7/7A
4
Slave 8/8A
Slave 9/9A
5
Slave 10/10A
Slave 11/11A
6
Slave 12/12A
Slave 13/13A
7
Slave 14/14A
Slave 15/15A
8
Slave 16/16A
Slave 17/17A
9
Slave 18/18A
Slave 19/19A
10
Slave 20/20A
Slave 21/21A
11
Slave 22/22A
Slave 23/23A
12
Slave 24/24A
Slave 25/25A
13
Slave 26/26A
Slave 27/27A
14
Slave 28/28A
Slave 2929A
15
Slave 30/30A
Slave 31/31A
16
reserved
Slave 1B
17
Slave 2B
Slave 3B
18
Slave 4B
Slave 5B
19
Slave 6B
Slave 7B
20
Slave 8B
Slave 9B