As-i circuit 1 as-i circuit 2 – EUCHNER AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor for 2 AS-i circuits User Manual
Page 104
104
Subject to reasonable modifications due to technical advances
Id.-No.: 103329
Issue date - 24.10.2008
EUCHNER GmbH + Co. KG
Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen
Tel. +49/711/75 97-0 • Fax. +49/711/753316
AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor
Operation in advanced display mod
Pressing the OK button continues with the actual test, ESC/SERVICE cancels the
process.
Now the new slave can be connected to the AS-i network. After connecting, the
current address of the slave is displayed as "OLD ADDRESS"and the message
"CONNECT NEW SLV" disappears.
To assign a new address to the slave the menu entry "NEW ADDRESS" must be
selected. Afterwards the new address can be selected by using the arrow but-
tons. The selected address is assigned by selecting "PRG" on the menu and
pressing the OK button.
If an error occurs while addressing a slave, one of the following error messages is
displayed for about 2 seconds:
SLAVE ADR TOOL
CONNECT NEW SLV
OLD ADDRESS
NEW ADDRESS
SLAVE ADR TOOL
CONNECT
OLD ADDRESS 21A
NEW ADDRESS 03B
PRG
Failed: SND: Slave with old address has not been detected.
Failed: SD0: Slave with address 0 already exists.
Failed: SD2: Chosen slave address already exists.
Failed: DE: AS-i slave address cannot be deleted.
Failed: SE: Error setting new address for AS-i slave.
Failed: AT: New address for AS-i slave could be stored temporarily only.
Failed: RE: Error reading extended ID1-code.
Information!
When working with a double master (AS-i master and two AS-i networks) the AS-i net-
work must be selected first by using the arrow and the OK buttons.
AS-I CIRCUIT 1
AS-i CIRCUIT 2