AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor
Function and startup of the Safety Monitor
Subject to reasonable modifications due to technical advances
Id.-No.: 103329
Issue date - 24.10.2008
EUCHNER GmbH + Co. KG
55
Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen
Tel. +49/711/75 97-0 • Fax. +49/711/753316
8.3
Safety-relevant documentation of the application
Proceed as follows:
•
Create the configuration of the AS-i Safety Monitor for your application.
•
Validate the configuration (done by the safety supervisor).
•
Print out the final configuration protocol and optionally the configuration over-
view (see Section 5.8 "Configuration documentation" in the software manual).
•
Sign the final configuration protocol (done by the safety supervisor).
•
Take the protocol for the safety-relevant documentation for your application
(machine documentation) and keep it in a safe place.
8.4
Diagnostic data
Diagnostics data can be obtained in any of 4 ways:
•
Display
•
PROFIBUS
•
ASIMON 3 G2 software over diagnostic port
•
AS-i Control Tools over diagnostic port or PROFIBUS
Attention!
Safety advisory:
Power must always be turned off when removing or inserting the chip card!
Ensure that the chip card contains the configuration intended for and released for
the application!
This can be done by comparing the release codes on the display (section
The safety representative who generated and validated the release code stores
the release code for the master configuration and approves use of the configura-
tion for specific equipment.
The person performing the startup reads out the release code on the display
before starting the equipment and compares it with the release code stored and
approved for the equipment.
After the chip card has been used to load the configuration into the device, the
safety functions of the device must be checked in the equipment.
Checking of the release code and testing the system must be documented in wri-
ting and is part of the system documentation.
Information!
The detailed description of the safety-relevant documentation of the configuration for
your application can be found in the separate software manual.
Information!
A detailed description of the setting for diagnostics mode is described in the section
“Setting diagnostics type” in the separate manual "AS-i 3.0 Command Inteface".