Det-Tronics PIRECL Infrared Hydrocarbon Gas Detector PointWatch Eclipse User Manual
Page 49

F-10
95-8526
14.2
3 output condition
Select and configure the output signal options for the Eclipse detector. Submenu options:
1 Config Gas Alarms. Submenu options inlcude:
1 High Alarm Level. The high alarm level cannot be set higher than 60% LEL or lower than the
low alarm level.
2 High Alarm Latch
3 Low Alarm Level. The low alarm level cannot be set lower than 5% LEL or higher than the
high alarm level.
4 Low Alarm Latch
NOTE
Refer to “Alarm Relays” in the Specifications section of this manual for important information regarding alarm relays.
2 Config fault out. Submenu options include:
1 Analog fault codes. This programs the analog output used to indicate faults. Submenu options
include:
–
Eclipse
– PIR 9400
– User defined
2 Analog code values. Submenu options include:
1 Warm up
2 Blocked Optics
3
Calibration
4
Fault
3 Hart output. Submenu options include:
1 Poll addr xx (address used by the host to identify a field device).
2 Num req preams x (Number of Request Preambles).
4 Com Port. Submenu options include:
1 EQ DIP switch xxx (used with Eagle Quantum systems only).
1 Protocol xxxx (protocol for RS-485 communications). Submenu options:
–
Modbus
–
ASCII
2 Poll addr xxx (polling address for RS-485 communications).
3 Baud Rate xxxx (baud rate for RS-485 communications). Submenu options include:
–
1200
–
2400
–
4800
–
9600
– 19.2k
4 Parity xxxx (parity for RS-485 communications). Submenu options include:
–
None
–
Even
–
Odd