14.2

3 output condition
Select and configure the output signal options for the Eclipse detector. Submenu options:

1 Config Gas Alarms. Submenu options inlcude:

1 High Alarm Level. The high alarm level cannot be set higher than 60% LEL or lower than the

low alarm level.

2 High Alarm Latch

3 Low Alarm Level. The low alarm level cannot be set lower than 5% LEL or higher than the

high alarm level.

4 Low Alarm Latch

NOTE

Refer to “Alarm Relays” in the Specifications section of this manual for important information regarding alarm relays.

2 Config fault out. Submenu options include:

1 Analog fault codes. This programs the analog output used to indicate faults. Submenu options

include:

Eclipse

– PIR 9400

– User defined

2 Analog code values. Submenu options include:

1 Warm up

2 Blocked Optics

3

Calibration

4

Fault

3 Hart output. Submenu options include:

1 Poll addr xx (address used by the host to identify a field device).

2 Num req preams x (Number of Request Preambles).

4 Com Port. Submenu options include:

1 EQ DIP switch xxx (used with Eagle Quantum systems only).

1 Protocol xxxx (protocol for RS-485 communications). Submenu options:

Modbus

ASCII

2 Poll addr xxx (polling address for RS-485 communications).

3 Baud Rate xxxx (baud rate for RS-485 communications). Submenu options include:

1200

2400

4800

9600

– 19.2k

4 Parity xxxx (parity for RS-485 communications). Submenu options include:

None

Even

Odd