Det-Tronics PIRECL Infrared Hydrocarbon Gas Detector PointWatch Eclipse User Manual

Page 14

background image

12

95-8526

14.2

Figure 14—Wiring terminal Identification

for Eagle Quantum Premier Eclipse

24 VDC –

24 VDC –

24 VDC +

24 VDC +

24 VDC SHIELD

24 VDC SHIELD

COM 1 A

COM 1 SHIELD

COM 1 B

COM 2 A

COM 2 B

COM 2 SHIELD

CALIBRATE

1

2

3

4

5

6

7

8

9

10

11

12

13

A2087

CURRENT OUTPUT

CHASSIS GROUND

POWER

SENSOR

EXTERNAL RESET

HIGH ALARM

HIGH ALARM / OC

AUX. ALARM

AUX. ALARM / OC

LOW ALARM

LOW ALARM / OC

FAULT

FAULT / OC

1

3

4

5

6

7

8

9

10

11

12

13

14

15

16

+

+

+

18 TO 32

VDC

POWER

SIGNAL

2

OC = OPEN COLLECTOR OUTPUT

(BASE MODEL ONLY)

A2202

24 VDC –

24 VDC +

– 4-20 MA

1

2

3

4

5

6

7

8

9

10

11

12

13

R8471H CONTROLLER

PIRECL

POINTWATCH ECLIPSE

+ 4-20 MA

24 VDC

24 VDC –

24 VDC +

+

2

1

NOTES: 1 INTERNAL JUMPER REQUIRED

FOR NON-ISOLATED CURRENT

OUTPUT (SINGLE POWER

SUPPLY).


2 250 OHM RESISTOR REQUIRED.

Figure 13—Standard Eclipse Wired to a Model R8471H Controller

CALIBRATE SWITCH

B2056

HOLD CALIBRATION MAGNET

AT OUTSIDE BASE OF JUNCTION

BOX AT THIS LOCATION

TO ACTIVATE CALIBRATION SWITCH

REMOTE LED

Figure 16—Remote Calibration Switch and LED in optional

Det-tronics PIRtB termination Box

Figure 15—Wiring the Model PIRECL for Benchtop testing/

Programming using HaRt Protocol

24 VDC –

24 VDC –

24 VDC +

24 VDC +

CALIBRATE

+ 4-20 MA

– 4-20 MA

RS-485 A

RS-485 B

RELAY POWER

FAULT

LOW ALARM

HIGH ALARM

NO USER

CONNECTION

1

2

3

4

5

6

7

8

9

10

11

12

13

A2203

24 VDC

+

250 TO 500 OHMS