beautypg.com

Appendix c – Det-Tronics PIRECL Infrared Hydrocarbon Gas Detector PointWatch Eclipse User Manual

Page 34

background image

c-1

95-8526

14.2

Appendix C

AteX ApprovAl Description

The following items, functions and options describe the ATEX approval.

ApprovAl
PointWatch Eclipse

®

Infrared Hydrocarbon Gas Detector, Model PIRECL Series.

0539

FM

APPROVED

®

II 2 G

Ex de IIC T4-T5 Gb
-- OR --
Ex de [ib] IIC T4-T5 Gb

(with HART communication port)

DEMKO 01 ATEX 129485X.

(Performance verified to Methane, Propane, Ethylene, and Butane in accordance with EN 60079-29-1).

T5 (Tamb –50°C to +40°C)

T4 (Tamb –50°C to +75°C)

IP66/IP67.
-- OR --

0539

FM

APPROVED

®

II 2 G

Ex d IIC T4-T5 Gb
-- OR --
Ex d [ib] IIC T4-T5 Gb

(with HART communication port)

DEMKO 01 ATEX 129485X.

(Performance verified to Methane, Propane, Ethylene, and Butane in accordance with EN 60079-29-1).

T5 (Tamb –55°C to +40°C)

T4 (Tamb –55°C to +75°C)

IP66/IP67.
HART Communication Port:

Uo = 4.0V

Co = 20μF

Io = 100mA

Lo = 500μH

performance testing to en60079-29-1:
The measuring function of the Infrared Gas Detector model PIRECL for explosion protection, according to

Annex II clause 1.5.5, 1.5.6 and 1.5.7 of the Directive 94/9/EC is, for methane, propane, ethylene, and butane, covered

in this EC-Type Examination Certificate in the following configurations:
1. PIRECL Infrared Gas Detector (LON Model) tested in combination with the EQP System Controller Model EQ3XXX.
2. PIRECL Infrared Gas Detector tested in combination with the Model PIRTB, Termination Box.
3. PIRECL Infrared Gas Detector tested as a stand-alone gas detector.