Det-Tronics PIRECL Infrared Hydrocarbon Gas Detector PointWatch Eclipse User Manual

Page 12

background image

10

95-8526

14.2

24 VDC

+

+

24 VDC –

24 VDC –

24 VDC +

24 VDC +

CALIBRATE

+ 4-20 MA

– 4-20 MA

RS-485 A

RS-485 B

RELAY POWER

FAULT

LOW ALARM

HIGH ALARM

1

2

3

4

5

6

7

8

9

10

11

12

13

NO USER CONNECTION

4 to 20 MA

B2051

*

*

TOTAL LOOP RESISTANCE = 250 OHMS MINIMUM, 600 OHMS MAXIMUM.

DO NOT INSTALL RESISTOR WITHIN PIRECL ENCLOSURE IN EEx e APPLICATIONS.

Figure 8—Eclipse Detector Wired for non-Isolated

4-20 ma Current output (Sourcing)

24 VDC

+

+

24 VDC –

24 VDC –

24 VDC +

24 VDC +

CALIBRATE

+ 4-20 MA

– 4-20 MA

RS-485 A

RS-485 B

RELAY POWER

FAULT

LOW ALARM

HIGH ALARM

1

2

3

4

5

6

7

8

9

10

11

12

13

NO USER CONNECTION

4 to 20 MA

B2050

*

TOTAL LOOP RESISTANCE = 250 OHMS MINIMUM, 600 OHMS MAXIMUM.

DO NOT INSTALL RESISTOR WITHIN PIRECL ENCLOSURE IN EEx e APPLICATIONS.

*

Figure 7—Eclipse Detector Wired for non-Isolated

4-20 ma Current output (Sinking)

24 VDC

+

24 VDC

+

24 VDC –

24 VDC –

24 VDC +

24 VDC +

CALIBRATE

+ 4-20 MA

– 4-20 MA

RS-485 A

RS-485 B

RELAY POWER

FAULT

LOW ALARM

HIGH ALARM

1

2

3

4

5

6

7

8

9

10

11

12

13

NO USER CONNECTION

+

4 to 20 MA

B2053

*

*

TOTAL LOOP RESISTANCE = 250 OHMS MINIMUM, 600 OHMS MAXIMUM.

DO NOT INSTALL RESISTOR WITHIN PIRECL ENCLOSURE IN EEx e APPLICATIONS.

Figure 10—Eclipse Detector Wired for Isolated

4-20 ma Current output (Sourcing)

24 VDC

+

24 VDC

+

24 VDC –

24 VDC –

24 VDC +

24 VDC +

CALIBRATE

+ 4-20 MA

– 4-20 MA

RS-485 A

RS-485 B

RELAY POWER

FAULT

LOW ALARM

HIGH ALARM

1

2

3

4

5

6

7

8

9

10

11

12

13

NO USER CONNECTION

+

4 to 20 MA

B2052

*

*

TOTAL LOOP RESISTANCE = 250 OHMS MINIMUM, 600 OHMS MAXIMUM.

DO NOT INSTALL RESISTOR WITHIN PIRECL ENCLOSURE IN EEx e APPLICATIONS.

Figure 9—Eclipse Detector Wired for Isolated

4-20 ma Current output (Sinking)