DeteCtable gaSeS
Eclipse is capable of detecting many hydrocarbon

gases and vapors. Refer to the Specifications section

of this manual for details.

oUtpUtS
Standard
The standard version provides an isolated/non-isolated

4-20 mA current loop for connection to analog input

devices.

optional relays
An optional relay output board providing two

programmable alarm relay outputs and one fault

relay output can be factory installed with the standard

version. All relays are sealed and provide form C (NO/

NC) contacts. The high and low alarm relay settings are

programmable and can be set for latching or non-latching

operation. The low alarm cannot be set above the high

alarm threshold. Alarm configuration can be done with

the HART or MODBUS interface. The onboard multicolor

LED indicates a LOW alarm condition via a flashing red

color, and a HIGH alarm condition via a steady red color.

The Eclipse internal magnetic switch or HART Field

Communicator can be used to reset latched alarms. A

short-duration magnetic switch activation of 1 second

will reset latched alarms. Holding the magnetic switch

closed for 2 seconds will start the calibration sequence.

The external calibration line will not reset latched alarm

relays.

When the optional relay output board is specified, the

PIRECL’s approval rating is Ex d only.

NOTE

Refer to “Alarm Relays” in the Specifications
section of this manual for important information
regarding alarm relays.

eQp Version
The Eagle Quantum Premier model provides proprietary

digital signals that are compatible with the EQ Premier

network (LON) only. No analog 4-20 mA or RS-485

MODBUS signal outputs are provided. The optional

onboard HART communication port is operational,

but is not recommended for programming use. All

programming of the EQP PIRECL detector should be

accomplished using the S3 point configuration software.

Refer to the EQP Appendix within this manual for

additional information.

Data logging Capability
Non-volatile memory is provided to save the 10 most

recent calibrations, alarm/fault events, and minimum/

maximum operating temperature history. An hour meter

(running operational hours since startup) is provided to

record operating service time and to give an indication

of the relative time between events. This information is

accessible using HART, MODBUS communication, or

EQP system software.

optional thirD party aDDreSSable MoDUleS
The PIRECL is electrically compatible with third party

addressable modules, provided the module fits within

the PIRECL wiring compartment. Whenever a third party

addressable module is installed, the PIRECL’s Ex e rating

and FM Approval are void, and only the Ex d rating is valid.

Installation of a third party addressable module requires a

specially labeled PIRECL model to ensure valid product

approvals.

SIGNAL PROCESSING

ELECTRONICS

GAS

CONCENTRATION

(LEL)

IR SOURCE

IR TRANSPARENT

WINDOW

OPTICAL

BEAM SPLITTER

MEASUREMENT

SIGNAL DETECTOR

REFERENCE

SIGNAL DETECTOR

OPTICAL

FILTERS

PERMEABLE

GAS CELL

SAPPHIRE

MIRROR

Figure 1—Measurement Scheme for Infrared Gas Detector