BAsic setUp sUBMenU
The tag number identifies a specific device. Changing units affects the engineering units

that are displayed. Re-ranging changes the analog output scaling.

1 tag
Press to access the Tag number menu. Enter the device tag number as desired.

2 pv Unit
Press to access PV Unit submenu. Select %LEL for standard combustible applications.

– % LEL

– ppm

– Vol %

3 range values
Press to access Range Values submenu.

1 URV 20-100% LEL (upper range value).

2 LRV 0% LEL (lower range value).

3 USL 100% LEL (upper sensor limit).

4 LSL 0% LEL (lower sensor limit).

4 Device information
Press to access device information submenu:

1 Tag xxxx

2 Date 6/30/2000

3 Descriptor (text associated with the field device that can be used by the operator in any way).

4 Message (text associated with the field device that can be used by the operator in any way).

5 Model: Eclipse

6 Write protect xx. This indicates whether variables can be written to the device, or whether commands

that cause actions to be performed in the device can or cannot occur.

7 Revision #’s. See Revision #’s submenu below.

8 Final asmbly num

9 Dev id xxxx (a number is used to identify a unique field device).

revision # submenu

offers selection options for:

1 Universal rev

2 Fld dev rev

3 Software rev xx

5 Gas
Type of gas being detected.

1 Tag

2 PV Unit xxxxx

3 Range Values

4 Device Information

5 Gas xxxxxx