Reset, Module 9 - f, Factry ) – Red Lion PAX2A User Manual

Page 31: Module 8 - a, Anlout ), Code, Type, Assign, Analog, Update

background image

31

Pro

9-FACtrY

P

COdE

50

FCS

Pro

NO

Factory

Service Code

mOdule 9 - f

aCTOry

s

erviCe

O

peraTiOns

(9-FACtrY)

PARAMETER MENU

RESTORE FACTORY DEFAULTS

Use the ! and @ keys to display COdE 66 and press

P. The meter will flash

rESEt

and then return to COdE 50. Press the

P key to return to Display Mode.

This will overwrite all user settings with the factory settings.

MODEL AND CODE VERSION

The meter will briefly display the model (P2A) on Line 1, and the current

firmware version (UEr x.xx) on Line 2, and then return to COdE 50.

CALIBRATION

NO Curr UoLt
OhMS tc

ICE

rtd AnLOut

The meter has been fully calibrated at the factory. Scaling to convert the input

signal to a desired display value is performed in Module 1. If the meter appears

to be indicating incorrectly or inaccurately, refer to Troubleshooting before

attempting to calibrate the meter. When recalibration is required (generally

every 2 years), it should only be performed by qualified technicians using

appropriate equipment. Calibration does not change any user programmed

parameters. However, it will affect the accuracy of the input signal and the

values previously stored using the Apply (APPLY) Scaling Style.

COdE

66

FCS

rESEt

COdE

50

FCS

P

COdE

51

FCS

P2A

V Er

x.xx

FCS

COdE

50

FCS

P

COdE

48

FCS

CAL

NO

FCS

P

Pro

NO

Pro

8-AnLOut

P

tYPE

4-20

AnL

ASSIGN

NONE

AnL

ANALOG

0.000

LO

ANALOG

100.00

HI

UPdAtE

0.0

AnL

brnAct

Lo

AnL

Analog Type Analog Output

Assignment

Analog Low

Scale Value

Analog High

Scale Value

Update

Time

Burn-out

Action

mOdule 8 - a

nalOg

O

uTpuT

p

arameTers

(8-AnLOut)

PARAMETER MENU

ANALOG OUTPUT TYPE

4-20 0-10 0-20

Enter the analog output type. For 0-20 mA or 4-20 mA use terminals 18 and

19. For 0-10 V use terminals 16 and 17. Only one range can be used at a time.

ANALOG OUTPUT ASSIGNMENT

NONE

rEL AbS

totAL Hi

Lo

S1

S2

S3

S4

Enter the source for the analog output to retransmit:

NONE

= Manual Mode operation. (See Module 7, Serial RLC Protocol).

rEL

= Relative (net) Input Value. The Relative Input Value is the Absolute Input

Value including the Display Offset Value.

AbS

= Absolute (gross) Input Value. The Absolute Input Value is the scaled input

value. It does not include the Display Offset Value.

totAL

= Totalizer Value

Hi

= Maximum Display Value

Lo

= Minimum Display Value

S1

-S4 = Setpoint Values

ANALOG LOW SCALE VALUE

-199999

to

999999

Enter the Display Value that corresponds to 0 mA (0-20 mA) , 4 mA (4-20

mA) or 0 VDC (0-10 VDC).

ANALOG HIGH SCALE VALUE

-199999

to

999999

Enter the Display Value that corresponds to 20 mA (0-20 mA) , 20 mA (4-20

mA) or 10 VDC (0-10 VDC).

ANALOG UPDATE TIME

0.0

to

10.0

Enter the analog output update rate in seconds. A value of 0.0 allows the

meter to update the analog output at the ADC Conversion Rate.

The following programming step is only available when Input Range in Module 1

is set for a temperature input (TC/RTD).

PROBE BURN-OUT ACTION

Hi Lo

Enter the probe burn-out action. In the event of a temperature probe failure,

the analog output can be programmed for low or high scale.

tYPE

4-20

AnL

ASSIGN

NONE

AnL

ANALOG

0

LO

ANALOG

10000

HI

UPdAtE

0.0

AnL

brnAct

Lo

AnL

This module is only accessible with the

optional PAXCDL Analog card installed.
Programming information contained in

this manual supercedes all

programming information included with

the PAXCDL card.

Temperature Input Only