Reset, Module 9 - f, Factry ) – Red Lion PAX2A User Manual
Page 31: Module 8 - a, Anlout ), Code, Type, Assign, Analog, Update

31
Pro
9-FACtrY
P
COdE
50
FCS
Pro
NO
Factory
Service Code
mOdule 9 - f
aCTOry
s
erviCe
O
peraTiOns
(9-FACtrY)
PARAMETER MENU
RESTORE FACTORY DEFAULTS
Use the ! and @ keys to display COdE 66 and press
P. The meter will flash
rESEt
and then return to COdE 50. Press the
P key to return to Display Mode.
This will overwrite all user settings with the factory settings.
MODEL AND CODE VERSION
The meter will briefly display the model (P2A) on Line 1, and the current
firmware version (UEr x.xx) on Line 2, and then return to COdE 50.
CALIBRATION
NO Curr UoLt
OhMS tc
ICE
rtd AnLOut
The meter has been fully calibrated at the factory. Scaling to convert the input
signal to a desired display value is performed in Module 1. If the meter appears
to be indicating incorrectly or inaccurately, refer to Troubleshooting before
attempting to calibrate the meter. When recalibration is required (generally
every 2 years), it should only be performed by qualified technicians using
appropriate equipment. Calibration does not change any user programmed
parameters. However, it will affect the accuracy of the input signal and the
values previously stored using the Apply (APPLY) Scaling Style.
COdE
66
FCS
rESEt
COdE
50
FCS
P
COdE
51
FCS
P2A
V Er
x.xx
FCS
COdE
50
FCS
P
COdE
48
FCS
CAL
NO
FCS
P
Pro
NO
Pro
8-AnLOut
P
tYPE
4-20
AnL
ASSIGN
NONE
AnL
ANALOG
0.000
LO
ANALOG
100.00
HI
UPdAtE
0.0
AnL
brnAct
Lo
AnL
Analog Type Analog Output
Assignment
Analog Low
Scale Value
Analog High
Scale Value
Update
Time
Burn-out
Action
mOdule 8 - a
nalOg
O
uTpuT
p
arameTers
(8-AnLOut)
PARAMETER MENU
ANALOG OUTPUT TYPE
4-20 0-10 0-20
Enter the analog output type. For 0-20 mA or 4-20 mA use terminals 18 and
19. For 0-10 V use terminals 16 and 17. Only one range can be used at a time.
ANALOG OUTPUT ASSIGNMENT
NONE
rEL AbS
totAL Hi
Lo
S1
S2
S3
S4
Enter the source for the analog output to retransmit:
NONE
= Manual Mode operation. (See Module 7, Serial RLC Protocol).
rEL
= Relative (net) Input Value. The Relative Input Value is the Absolute Input
Value including the Display Offset Value.
AbS
= Absolute (gross) Input Value. The Absolute Input Value is the scaled input
value. It does not include the Display Offset Value.
totAL
= Totalizer Value
Hi
= Maximum Display Value
Lo
= Minimum Display Value
S1
-S4 = Setpoint Values
ANALOG LOW SCALE VALUE
-199999
to
999999
Enter the Display Value that corresponds to 0 mA (0-20 mA) , 4 mA (4-20
mA) or 0 VDC (0-10 VDC).
ANALOG HIGH SCALE VALUE
-199999
to
999999
Enter the Display Value that corresponds to 20 mA (0-20 mA) , 20 mA (4-20
mA) or 10 VDC (0-10 VDC).
ANALOG UPDATE TIME
0.0
to
10.0
Enter the analog output update rate in seconds. A value of 0.0 allows the
meter to update the analog output at the ADC Conversion Rate.
The following programming step is only available when Input Range in Module 1
is set for a temperature input (TC/RTD).
PROBE BURN-OUT ACTION
Hi Lo
Enter the probe burn-out action. In the event of a temperature probe failure,
the analog output can be programmed for low or high scale.
tYPE
4-20
AnL
ASSIGN
NONE
AnL
ANALOG
0
LO
ANALOG
10000
HI
UPdAtE
0.0
AnL
brnAct
Lo
AnL
This module is only accessible with the
optional PAXCDL Analog card installed.
Programming information contained in
this manual supercedes all
programming information included with
the PAXCDL card.
Temperature Input Only