User-n – Red Lion PAX2A User Manual
Page 15

15
RESET MINIMUM DISPLAY
When activated (momentary action), rESEt flashes and the Minimum resets
to the present Input Display value. The Minimum function then continues from
that value. This selection functions independent of the selected display.
RESET MAXIMUM AND MINIMUM DISPLAY
When activated (momentary action), rESEt flashes and the Maximum and
Minimum readings are set to the present Input Display value. The Maximum and
Minimum function then continues from that value. This selection functions
independent of the selected display.
DISPLAY SELECT
When activated (momentary action), Line 2 advances
to the next display that is not locked out from the Display
Mode.
ADJUST DISPLAY INTENSITY
When activated (momentary action), the display intensity changes to the next
intensity level.
CHANGE DISPLAY COLOR
When activated (momentary action), Line 1 will change
color.
SELECT PARAMETER LIST
Two lists of input scaling points and setpoint values (including band and
deviation) are available. The two lists are named LISt-A and LISt-b. If a user
input is used to select the list then LISt-A is selected when the user input is not
active and LISt-b is selected when the user input is active (maintained action).
If a front panel key is used to select the list then the list will toggle for each key
press (momentary action). The display will only indicate which list is active
when the list is changed. To program the values for LISt-A and LISt-b, first
complete the programming of all the parameters. Exit programming and switch
to the other list. Re-enter programming and enter the desired values for the input
scaling points, setpoints, band, and deviation if used.
SETPOINT SELECTIONS
The following selections are functional only with a Setpoint plug-in card
installed.
r-1
-
Reset Setpoint 1 (Alarm 1)
r-2
-
Reset Setpoint 2 (Alarm 2)
r-3
-
Reset Setpoint 3 (Alarm 3)
r-4
-
Reset Setpoint 4 (Alarm 4)
r-34
- Reset Setpoint 3 & 4 (Alarm 3 & 4)
r-234
- Reset Setpoint 2, 3 & 4 (Alarm 2, 3 & 4)
r-ALL
- Reset All Setpoints (Alarms 1-4)
PRINT REQUEST
The meter issues a block print through the serial port when activated, and the
serial type is set to rLC. The data transmitted during a print request and the serial
type is programmed in Module 7. If the user input is still active after the
transmission is complete (about 100 msec), an additional transmission occurs.
As long as the user input is held active, continuous transmissions occur.