beautypg.com

Setpnt, Bn-dev, Hyster – Red Lion PAX2A User Manual

Page 21: T-on, T-off, Logic, Reset, Stndby, Annun, Color

background image

21

SETPOINT VALUE

-199999

to

999999

Enter desired setpoint alarm value. Setpoint values can also be entered in the

Display Mode during Program Lockout when the setpoint is programmed as
ENt

in Parameter Module 3. The decimal point position is determined by the

Setpoint Assignment value.

BAND/DEVIATION VALUE

-199999

to

999999

This parameter is only available in band and deviation setpoint actions. Enter

desired setpoint band or deviation value. When the Setpoint Action is

programmed for Band, this value can only be a positive value.

HYSTERESIS VALUE

1

to

65000

Enter desired hysteresis value. See Setpoint Alarm Figures for visual

explanation of how setpoint alarm actions (balanced and unbalanced) are

affected by the hysteresis. When the setpoint is a control output, usually balanced

hysteresis is used. For alarm applications, usually unbalanced hysteresis is used.

For unbalanced hysteresis modes, the hysteresis functions on the low side for

high acting setpoints and functions on the high side for low acting setpoints.

Note: Hysteresis eliminates output chatter at the switch point, while time delay

can be used to prevent false triggering during process transient events.

ON TIME DELAY

0.0

to

3275.0

seconds

Enter the time value in seconds that the alarm is delayed from turning on after

the trigger point is reached. A value of 0.0 allows the meter to update the alarm

status per the response time listed in the Specifications. When the output logic

is rEv, this becomes off time delay. Any time accumulated at power-off resets

during power-up.

OFF TIME DELAY

0.0

to

3275.0

seconds

Enter the time value in seconds that the alarm is delayed from turning off after

the trigger point is reached. A value of 0.0 allows the meter to update the alarm

status per the response time listed in the Specifications. When the output logic

is rEv, this becomes on time delay. Any time accumulated at power-off resets

during power-up.

OUTPUT LOGIC

nor rEv

Enter the output logic of the alarm output. The nor logic leaves the output

operation as normal. The rEv logic reverses the output logic. In rEv, the alarm

states in the Setpoint Alarm Figures are reversed.

RESET ACTION

Auto

LAtCh1s

LAtCh2

Enter the reset action of the alarm output.

Auto

= Automatic action; This action allows the alarm output to automatically

reset off at the trigger points per the Setpoint Action shown in Setpoint Alarm

Figures. The “on” alarm may be manually reset (off) immediately by a front

panel function key or user input.The alarm remains reset off until the trigger

point is crossed again.

LAtCh1

= Latch with immediate reset action; This action latches the alarm

output on at the trigger point per the Setpoint Action shown in Setpoint Alarm

Figures. Latch means that the alarm output can only be turned off by front

panel function key or user input manual reset, serial reset command or meter

power cycle. When the user input or function key is activated (momentary or

maintained), the corresponding “on” alarm output is reset immediately and

remains off until the trigger point is crossed again. (Previously latched alarms

will be off if power up Display Value is lower than setpoint value.)

LAtCh2

= Latch with delay reset action; This action latches the alarm output on

at the trigger point per the Setpoint Action shown in Setpoint Alarm Figures.

Latch means that the alarm output can only be turned off by front panel

function key or user input manual reset, serial reset command or meter power

cycle. When the user input or function key is activated (momentary or

maintained), the meter delays the event until the corresponding “on” alarm

output crosses the trigger off point. (Previously latched alarms are off if

power up Display Value is lower than setpoint value. During a power cycle,

the meter erases a previous Latch 2 reset if it is not activated at power up.)

SETPOINT STANDBY OPERATION

NO YES

When YES, the alarm is disabled (after a power up) until the trigger point is

crossed. Once the alarm is on, the alarm operates normally per the Setpoint

Action and Reset Mode.

SETPOINT ANNUNCIATOR

nor

rEv

FLASh

OFF

The OFF mode disables display setpoint annunciators. The nor mode

displays the corresponding setpoint annunciators of “on” alarm outputs. The
rEv

mode displays the corresponding setpoint annunciators of “off” alarms

outputs. The FLASh mode flashes the corresponding setpoint annunciators of

“on” alarm outputs.

LINE 1 CHANGE COLOR

NO CHG

GrEEN

OrANGE

rEd

GrnOrG

rEdOrG

rEdGrn

LINE 1

This parameter allows the Line 1 Display to change color, or alternate

between two colors, when the alarm is activated. When multiple alarms are

programmed to change color, the highest numbered active alarm (S4-S1)

determines the display color.

The NO CHG selection will maintain the color displayed prior to the alarm

activation. The LINE 1 selection sets the display to the Line 1 Display Color

(Color), programmed in Module 3.

The following programming step is only available when Input Range in Module 1

is set for a temperature input (TC/RTD).

PROBE BURN-OUT ACTION

OFF ON

Enter the probe burn-out action. In the event of a temperature probe failure

(TC open; RTD open or short), the output can be programmed to be on or off.

SEtPNt

100

Sn

bn-dEV

0

dn

HYStEr

2

Sn

t-ON

0.0

Sn

t-OFF

0.0

Sn

LOGIC

nor

Sn

rESEt

Auto

Sn

StndbY

NO

Sn

Annun

nor

Sn

Color

NO CHG

Sn

brnAct

OFF

Sn

ALARM

STATE

OFF

ON

Hys

SP

OFF

ON

OFF

OFF

ON

OFF ON

OFF

OFF

ON

OFF

ON

OFF

MANUAL

RESET

SP - Hys

( Auto)

(LAtC1)

(LAtC2)

м

н

о

Setpoint Alarm Reset Actions