Generic wind calculation, Figure 37, Calculations view: selection of sample interval – Vaisala Hydromet Data Collection Platform User Manual
Page 89

Chapter 4 ____________________________________________ Basic Use of Lizard Setup Software
VAISALA_______________________________________________________________________ 87
5.
Open the same view where you made a copy of the calculation.
6.
In the Utility menu, select Paste.
7.
As the latter setup does not necessarily contain the same variables,
all references to the variables have been lost (that is, all variable
references are empty) and you have to reconnect them. This
procedure is analogous to defining the input variables for a new
calculation.
Generic Wind Calculation
You can configure the sample interval of a generic wind calculation to
be either 0.25 s, 0.5 s, 1 s, or 2 s. The sample interval should match the
sampling rate defined for the wind sensor. For example, if you want to
calculate wind with 4 Hz (250 ms) sampling, you must set the
QMW101 measurement sampling rate to 250 ms (0.25 s) and the
calculation sampling interval to 0.25 s (250 ms); see
.
0711-059
Figure 37
Calculations View: Selection of Sample Interval