HP ESL E-series Tape Libraries User Manual
Page 119
Sense
key
ASC
ASCQ Message name / description
5
87
F0
DEPTH INVALID COMMAND
Depth hardware commanded to position out of system mechanical limits.
•
Run the Robotics to Home Position test from the OCP.
•
If the problem persists, calibrate the library.
•
Verify that the host software application is supported, has up-to-date
patches, and is correctly configured.
•
Verify that the library and its components have the current firmware.
5
1A
00
PARAMETER LIST LENGTH ERROR
Invalid parameter list length field specified by command.
•
Verify that the host software application is supported, has up-to-date
patches, and is correctly configured.
•
Verify that the library and its components have the current firmware.
5
2C
00
COMMAND SEQUENCE ERROR (read of unwritten echo buffer)
5
3A
00
MEDIUM NOT PRESENT
The inventory indicated that a cartridge was in this bin but no cartridge
was sensed by the picker when it attempted to pick it. It may also
indicate that the tape is not ready to be picked from the drive because
the tape is not fully unloaded.
•
Retry the command.
•
Check for proper seating of the cartridge.
5
3B
0D
MEDIUM DESTINATION ELEMENT FULL
Destination element address already contains a cartridge.
•
Re-inventory the cabinet and retry the move command using your
application software.
•
If the problem recurs, run the Robotics to Home Position test followed
by a cabinet inventory, and retry the move command using your
application software.
5
3B
0E
MEDIUM SOURCE ELEMENT EMPTY
Source element address does not contain a cartridge.
•
Re-inventory the cabinet and retry move command using your
application software.
•
If the problem recurs, run the Robotics to Home Position test followed
by a cabinet inventory, and retry the move command using your
application software.
5
4E
00
OVERLAPPED COMMANDS ATTEMPTED
Due to a second command being sent from the same host before a
previous command has completed, the previous command has been
aborted. This may also occur when executing off-line commands via the
control panel and DIAG port simultaneously.
•
Verify that the host software application is supported, has up-to-date
patches, and is correctly configured.
•
Verify that the library and its components have the current firmware.
5
8A
02
UNCALIBRATED POSITION
System requires calibration. Run the Calibrate Cabinet test from the OCP.
5
8B
E0
CLM INVALID START CONDITION
CLM hardware condition is unknown. Run the Robotics to Home Position
test.
HP StorageWorks
119