Adjusting the Open-Time for the Hi Static Pressure Alarm
The Open-Time of the tunnel curtain or vent doors, in case a Hi static

pressure alarm occurs, can be adjusted from 0 to 900 sec.

Set the function to "21.Alarm Limits" from the main menu using

the navigation buttons.

Use the navigation buttons to select "2.Static Pressure" then press

the right-arrow key.

Press the right-arrow key once

again in order to select the "3.Hi

Static Alarm" option. The opening

time of vent doors and of the tunnel

curtain are displayed.

Use the adjustment buttons to adjust vents doors' Open-Time.

Press the down-arrow key once to select curtain's Open-Time.

Use the adjustment buttons to adjust curtain's Open-Time.

5.13.3 Resetting the Alam Log

Resetting the alarm log can only be performed from the installer mode.

Set the function to "19.Installation" from the main menu using the

navigation buttons then press the right-arrow key. The "Clear

Alarms" menu is selected. Note that this menu is only accessible

from the installer mode (see sec. 5.14.2).

Use the adjustment buttons to select "Yes", in order to clear the

alarm log. The answer is validated after an 8 second delay or when

the user exits the menu.

Hi Static Alarm

Open Vents sec 30

Open Tunnel sec 30