Static Settings 2

Outside Temperature

Influence: 50.0°F

Close At: .070”WC

Open At: .090”WC

Use the adjustment buttons to select the fan stage above which the

second group of static pressure set points starts being used.

Press the down-arrow key once, the LO static pressure set point #2

is selected

(Close At).

Use the adjustment buttons to adjust the 2nd low static pressure set

point

(Close At) to the desired value then press the down-arrow key.

The HI static pressure set point #2

(Open At) is selected.

Use the adjustment buttons to adjust the 2nd HI static pressure set

point

(Open At) to the desired value.

Press the left-arrow key to exit this menu.

5.5.2.5 2nd Group of Pressure Set Points: at Outside T° X

The following procedure shows how to select the outside temperature

below which the second group of static pressure set points starts being

used. It also explains how to adjust the second group of Hi and Lo static

pressure set points

(Open At and Close At). Refer to sec.5.14.3 to

activate this function.

Select "8.Vents/Static P" from the main menu using the navigation

buttons then press the right-arrow key. Note that this menu is only

available if the static pressure sensor has been enabled during the

installation setup (see sec 5.14.3).

Press the right-arrow key to select the "1.Set Points" menu.

Press the down-arrow key in order

to the select "Outside Temperature

Influence" display. Note that this

menu only appears if the outside

temperature has been enabled

during the installation setup and if

the 2nd Group of static pressure set

points has been enabled (see sec

5.14.3).