5.5 INLET / VENT DOOR SETTINGS

The PP-32 controller can operate the air inlets / vent doors in two

different ways:

1. Inlets' positions can be determined by using a potentiometer feedback

controller (DWR-F-1A). Refer to the installation setup section to

enable DWR-F-1A modules. Note that the static pressure sensor must

be deactivated in order to activate the air inlets (see sec. 5.15.3).

2. Inlets' positions can be determined by the static pressure level in the

barn. In this case, a static pressure sensor is required and must be

activated during the installation setup (see sec. 5.15.3). The term

"Vent Door" is used to refer to an air inlet that is controlled by the

static pressure.

5.5.1 Inlet Settings (Potentiometer Feedback from Inlets)

If air inlets operate according to potentiometer feedback modules (DWR-

F-1A), the PP-32 controller adjusts the air inlets opening according to

ventilation stages. As the temperature increases and new stages are

activated, the inlet is opened or closed accordingly. The air inlet position

is directly related to these ventilation stages. Refer to the DWR-F-1A

instruction manual to program inlet openings.

In addition, a compensation can be activated to ensure the uniformity in

room temperature: air inlet positions are automatically adjusted when the

reading of the sensors that are associated with the air inlet differs from

the average room temperature.

5.5.1.1 Setting DWR-F-1A's ID numbers

ID numbers must be assigned to each DWR-F-1A modules. This allows to

establish the communication with the PP-32 control and the external

modules. The following table gives the proper ID numbers for each
DWR-F-1A module.