Open Time: when the static pressure exceeds the Hi pressure set point,

the curtain opens during this delay. It ranges from 0 to 900 seconds.

Close Time: when the static pressure drops below the Lo pressure set

point, the curtain closes during this delay. It ranges from 0 to 900 sec.

Off Time: once the curtain has opened or closed (depending on the

situation) it then stops operating during this delay. The Off Time delay

ranges from 0 to 900 seconds.

Select "9.Tunnel Curtain" from the main menu using the navigation

buttons then press the right-arrow key. Note that this menu is only

available if the tunnel curtain has been enabled during the installation

setup (see sec 5.14.3).

Press the right-arrow key once to select "1.Set Points" menu.

Press the down-arrow key in order

to select the "Open Time" display.

Use the adjustment buttons to

adjust the Open Time. Note that

this menu only appears if the

curtain operates in static pressure

mode (see sec 5.14.3).

Press the down-arrow key in once. The Close Time is selected. Use

the adjustment buttons to set the Close Time to the desired value.

Press the down-arrow key in once. The Off Time is selected. Use the

adjustment buttons to set the Off Time to the desired value.

Open At: .080”WC

Open Time 60sec

Close Time 60sec

Off Time 10sec

CURTAIN'S TIMER

ON

OPEN / CLOSE

TIMES

OFF
TIME