2 table of possible error messages, On 6.2) – NORD Drivesystems BU0135 User Manual

Page 78

background image

SK 105E…175E Motor Starter Manual

78

Pre-series version

BU 0135 GB-2713

6.2 Table of possible error messages

Display in the
SimpleBox

Fault

Text in the Parameter Box

Cause

Remedy

Group

Details in
P700[-01] /
P701

E002

2.0

Overtemp. Motor PTC
„"Overtemperature of motor
PTC“

(from thermistor)

Motor temperature sensor has triggered

Reduce motor load

E003

3.0

I

2

t overcurrent limit

Continuous motor overload

Motor overcurrent from I

2

t calculation

E005

5.1

Overvoltage mains

Mains voltage is too high

Please check 200V-10% … 500V+10%

E006

6.1

Mains undervoltage

Mains voltage is too low

Please check 200V-10% … 500V+10%

E007

7.0

Phase error

A mains phase is not connected.

Check the mains connection

E016

16.0

Motor phase error

A motor phase is not connected.

Check P539, check motor connection

16.1

Magn. current monitoring
"Magnetisation current
monitoring"

Required excitation current not achieved at moment of
switch-on.

Check P539, check motor connection

E020

E021

20.1

Watchdog

System error in program execution, triggered by EMC
interference.

Please comply with wiring guidelines in Section 2.3.

Use additional external mains filter. (Section 7.3 / 7.4 EMC)

The motor starter must be very well earthed.

20.2

Stack overflow

20.3

Stack underflow

20.4

Undefined opcode

20.5

Protected Instruct.
„Protected Instruction“

20.6

Illegal word access

20.7

Illegal Inst.

Access

“Illegal Instruction Access”

20.8

Prog.mem. error
"Program memory error"
(
EEPROM error)

20.9

Memory Protection Error

21.0

NMI error
(not used by hardware)

21.1

PLL error

21.2

ADU error

21.3

PMI error

21.4

Userstack overflow