5 Parameterisation

BU 0135 GB-2713

Pre-series version

75

Parameter

{ Factory setting }

Setting value / Description / Note

READ

RAM

READ /

FLASH

FLASH

P741

[-01]

...

[-09]

Process data Bus Out

(Process data Bus Out)

S

0000 ... FFFF

(hex)

This parameter provides information about the actual status word and the actual values that are
transferred via the bus systems.

[-01] = Status word

Status word

[-02] = Actual value 1

(error number in the High Byte and warning number in the Low Byte)

[-03] = Actual value 2

(actual current related to the nominal current of the device)

[-04] = Actual value 3

(actual effective power related to the rated power of the device)

[-05] = Parameter data Out 1

[-06] = Parameter data Out 2

[-07] = Parameter data Out 3

[-08] = Parameter data Out 4

[-09] = Parameter data Out 5

Data during parameter transfer.

P743

Device type

(Device type)

x

0.25 ... 11.00 kW

Displays the nominal motor starter power in kW, e.g. "3.00"

Þ starter with 3.0 kW nominal

power.

P744

Configuration level

(Configuration level)

x

0 ... 11

This parameter displays the versions integrated into the motor starter.

0 = 105E

1 = 115E

2 = 125E

3 = 135E

4 = 145E (AS-i)

5 = 155E (AS-i)

6 = 165E (AS-i)

7 = 175E (AS-i)

8 = 145E (PBR)

9 = 155E (PBR)

10 = 165E (PBR)

11 = 175E (PBR)

P749

Status of DIP switches

(Status of DIP switches)

x

0000 ... 000F

(hex)

or

0 ... 15

(dec)

This parameter shows the actual setting of the motor starter DIP switch "S1" (see Section
4.2.2.2).

Bit 0:

Bit 1:

Bit 2:

Bit 3:

DIP switch 1

DIP switch 2

DIP switch 3

DIP switch 4

P762

U phase voltage

(U phase voltage)

x

0 ... 999 V

Displays the actual U phase voltage.

NOTE:

This value can deviate somewhat from the value in P722, due to the measurement
procedure used, even with symmetrical output currents.