NORD Drivesystems BU0135 User Manual
Page 75
5 Parameterisation
BU 0135 GB-2713
Pre-series version
75
Parameter
{ Factory setting }
Setting value / Description / Note
READ
RAM
READ /
FLASH
FLASH
P741
[-01]
...
[-09]
Process data Bus Out
(Process data Bus Out)
S
0000 ... FFFF
(hex)
This parameter provides information about the actual status word and the actual values that are
transferred via the bus systems.
[-01] = Status word
Status word
[-02] = Actual value 1
(error number in the High Byte and warning number in the Low Byte)
[-03] = Actual value 2
(actual current related to the nominal current of the device)
[-04] = Actual value 3
(actual effective power related to the rated power of the device)
[-05] = Parameter data Out 1
[-06] = Parameter data Out 2
[-07] = Parameter data Out 3
[-08] = Parameter data Out 4
[-09] = Parameter data Out 5
Data during parameter transfer.
P743
Device type
(Device type)
x
0.25 ... 11.00 kW
Displays the nominal motor starter power in kW, e.g. "3.00"
Þ starter with 3.0 kW nominal
power.
P744
Configuration level
(Configuration level)
x
0 ... 11
This parameter displays the versions integrated into the motor starter.
0 = 105E
1 = 115E
2 = 125E
3 = 135E
4 = 145E (AS-i)
5 = 155E (AS-i)
6 = 165E (AS-i)
7 = 175E (AS-i)
8 = 145E (PBR)
9 = 155E (PBR)
10 = 165E (PBR)
11 = 175E (PBR)
P749
Status of DIP switches
(Status of DIP switches)
x
0000 ... 000F
(hex)
or
0 ... 15
(dec)
This parameter shows the actual setting of the motor starter DIP switch "S1" (see Section
4.2.2.2).
Bit 0:
Bit 1:
Bit 2:
Bit 3:
DIP switch 1
DIP switch 2
DIP switch 3
DIP switch 4
P762
U phase voltage
(U phase voltage)
x
0 ... 999 V
Displays the actual U phase voltage.
NOTE:
This value can deviate somewhat from the value in P722, due to the measurement
procedure used, even with symmetrical output currents.