4 other options, 3 commissioning information – NORD Drivesystems BU0135 User Manual

Page 38

background image

SK 105E…175E Motor Starter Manual

38

Pre-series version

BU 0135 GB-2713

2.8.2.4

Other options

M12 sockets and plugs for installation in the housing box of the basic device or in technology units may only
be used if they are approved for use in ATEX Zone 22 3D.

Name

Part Number

Approved for

ATEX Zone 22 3D

Not approved for

ATEX Zone 22 3D

SK TIE4-WMK-1

275274000

x

SK TIE4-WMK-2

275274001

x

SK TIE4-WMK-TU

275274002

x

SK TIE4-HAN10E

275274100

x

SK TIE4-HANQ5

275274110

x

SK TIE4-SWITCH

275274610

x

SK TIE4-M12-M16

275274510

x

SK TIE4-M12-PBR

275274500

x

SK TIE4-M12-AS1

275274502

x

SK TIE4-M12-AS1-AUX

275274513

x

SK TIE4-M12-INI

275274503

x

SK TIE4-M12-POW

275274507

x

2.8.3

Commissioning information

For Zone 22 the cable glands must at least comply with protection class IP 55. Unused openings must be
closed with blank screw caps suitable for ATEX Zone 22 3D (minimum protection class IP 55).

The motors are protected against overheating by means of the motor starter. This is carried out by the
evaluation of the motor PTC in the motor starter. In order to ensure this function, the PTC must be
connected to the intended input (Terminal 38/39 control terminal plug connector). In addition, care must be
taken that the nominal current of the motor is adjusted accordingly.

Overview of the necessary parameter settings:

Parameter

Setting value

Factory setting

Description

P203

Motor data

Data according to rating
plate

[xxx]

If a 4-pole NORD motor is not used, the nominal
current on the rating plate must be entered here.

P535

I²t motor

According to motor and
ventilation

[0]

The I²t- monitoring of the motor must be switched
on. The set values depend on the type of
ventilation and the motor used. See
Planning Guideline No.: 605 2101