SK 105E…175E Motor Starter Manual
62
Pre-series version
BU 0135 GB-2713
5.1.1
Operating displays
Parameter
{ Factory setting }
Setting value / Description / Note
READ
RAM
READ /
FLASH
FLASH
P000
Operating para. disp.
(Operating parameter display)
x
0.01 ... 9999
In the SimpleBox (SK CSX-3H) display, the parameter value online selected in P100 is
displayed.
P001
Select of disp.value
(Selection of display value)
x
0 ... 11
{ 0 }
0 = Actual frequency [Hz], is the actual output frequency being supplied by the starter.
1 = Mains frequency [Hz], is the frequency of the mains voltage.
2 = Current [A], the actual output current measured by the starter.
3 = Effective current [A], is the effective current which is supplied by the motor starter.
4 = Reactive current [A], is the reactive current which is supplied by the motor starter.
5 = Mains voltage [V~ ], is the voltage which is applied to the input of the starter.
6 = cos phi, the currently calculated value of the power factor.
7 = Apparent power [kVA], the actual apparent power calculated by the starter.
8 = Effective power [kW], the actual effective power calculated by the starter.
9 = Mains phase sequence, 0 = right hand field of rotation, 1 = left hand field of rotation.
10 = Degree of phase control [%].
11 = Actual current amplification
P003
Supervisor code
(Supervisor code)
x
0 ... 9999
{ 1 }
0 = The Supervisor parameters are not visible. Otherwise, all parameters are visible.
1 = All parameters are visible
.
2 = ... 9999, (except 65) only parameters P001 and P003 are visible.
10
In the following, supervisor parameters are designated with "S"; normal parameters are designated with "x"