beautypg.com

2 dip switches – NORD Drivesystems BU0135 User Manual

Page 47

background image

4 Commissioning

BU 0135 GB-2713

Pre-series version

47

4.2.2.2

DIP switches

Individual functions of the motor starters can be set by means of a quadruple DIP switch. These differ ac-
cording to the equipment version.

DIP
switches

Functionality

Functionality

105E

145E

115E

155E

125E

165E

135E

175E

DIP1

Automatic start

0: Enable with flank

1: Enable with level

+

+

+

+

DIP2

Phase sequence
detection

0: According to phase sequence

Mains connection

1: According to phase sequence

Required direction of rotation

à

Automatic detection of

phase sequence

+

+

DIP2

Switch off with error in
case of
overtemperature

0: Starter switches off on

overtemperature

1: No switch off on

overtemperature

à

only warning

+

*

DIP3

Release the brake

0: Brake released on

enable

1: Brake is permanently

released

+

+

DIP4

Switch off with error in
case of
overtemperature

0: Starter switches off on

overtemperature

1: No switch off on

overtemperature

à

only warning

+

+

*

DIP3, 4

Switch-off ramp

00: Deceleration mode 1

01: Deceleration mode 2

10: Deceleration mode 3

11: Deceleration mode 4

+

+

* For SK 135E and SK 175E devices the function "Switch off with error on overtemperature" can only be ena-
bled via parameter P580.

4 3 2 1

ON
OFF