NORD Drivesystems BU0135 User Manual
Page 68
SK 105E…175E Motor Starter Manual
68
Pre-series version
BU 0135 GB-2713
Parameter
{ Factory setting }
Setting value / Description / Note
READ
RAM
READ /
FLASH
FLASH
P428
Automatic starting
(Automatic starting)
x
0 ... 1
{ 0 }
In the standard setting (P428 = 0
à Off) the motor starter requires a flank to enable (signal
change from "Low
à High") at the relevant digital input. In the setting
(P428 = On
à 1) the motor starter reacts to a High level.
NOTE: As long as P130=0 is set, P428 is determined via the DIP switch S1. In this case the
parameter can only be read, but not changed. It corresponds to the value which is determined
by the DIP switch setting.
P434
[-01]
…
[-03]
Digital output function
(Digital output function)
x
0 ... 3
{ [-01] = 1 }
Dig.1/Bus.Bit 0
Output
{ [-02] = 2 }
Dig.2/Bus.Bit 1
Output { [-03] = 3 }
Mechanical
brake
Here the set functions for up to three digital outputs can be viewed. It is possible to change the
setting if parameter P130=1 is set. Otherwise the value can only be views and is fixed.
0 = No function
1 = fault / warning
2 = Motor running
3 = Mechanical brake
P499
[-01]
…
[-04]
Fnct. DIP switches
(DIP switch function)
x
0 ... 6
{ [-01] = 1 }
{ [-02] = 2 }
{ [-03] = 5 }
{ [-04] = 6 }
Here the set functions for up to four DIP switches can be viewed. It is not possible to change the
setting.
0 = Switched off
1 = Automatic start
2 = Phase sequence detection
3 = Release the brake
4 = Overtemperature switch-off on error.
5 = Switch-off mode Bit 0
6 = Switch-off mode Bit 1
14
The function of the output for the mechanical brake cannot be changed.