5 Parameterisation

BU 0135 GB-2713

Pre-series version

73

Parameter

{ Factory setting }

Setting value / Description / Note

READ

RAM

READ /

FLASH

FLASH

P709

[-01]

...

[-04]

Potentiomet. status

(Potentiometer status)

x

0.0 ... 100.0 %

Displays the measured analog input value at the potentiometers.

[-01] =

Potentiometer 1

[-02] =

Potentiometer 2

[-03] =

Potentiometer 3

[-04] =

Potentiometer 4

P711

Digital output status

(Status of digital output)

x

0000 ... 0111

(bin)

or

00 ... 07

(hex)

Indicates the actual status of the digital outputs of the motor starter.

Bit 0 = Digital output 1
Bit 1 = Digital output 2
Bit 2 = mechanical brake

Bits 3-0

Minimum value

0000

0

Binary

hex

Maximum value

0111

7

Binary

hex

SimpleBox: The binary Bits are converted into a hexadecimal value and displayed.

ParameterBox: The Bits are displayed with increasing values from right to left (binary).

P716

Actual frequency

(Actual frequency)

x

-70.0 ... 70.0 Hz

Displays the actual output frequency. This is calculated from the mains frequency and the
selected direction of rotation on enabling. "0" is output when the device is switched off.

P718

Mains frequency

(Mains frequency)

x

-70.0 ... 70.0 Hz

Displays the mains frequency determined by the motor starter.

P719

Actual current

(Actual current)

x

0.0 ... 999.9 A

Displays the actual output current.

P720

Effective current

(Actual effective current)

x

-999.9 ... 999.9 A

Displays the actually measured effective current.

à negative values = generator, à positive values = drive

P721

Reactive current

(Actual reactive current)

x

-999.9 ... 999.9 A

Displays the actually measured reactive current.

P722

Current voltage

(Actual voltage)

x

0 ... 500 V

Displays the actual AC voltage supplied by the motor starter output.

P723

Voltage -d

(Actual voltage component Ud)

S

0 ... 500 V

Usually this value is "0"