NORD Drivesystems BU0135 User Manual
Page 74
SK 105E…175E Motor Starter Manual
74
Pre-series version
BU 0135 GB-2713
Parameter
{ Factory setting }
Setting value / Description / Note
READ
RAM
READ /
FLASH
FLASH
P724
Voltage -q
(Actual voltage component Uq)
S
0 ... 500 V
This value usually corresponds to the value in parameter P722.
P725
Actual cos phi
(Actual cos
j
)
x
0.00 ... 1.00
Displays the actual calculated cos
j of the drive.
P726
Apparent power
(Apparent power)
x
0.00 ... 99.99 kVA
Displays the actual calculated apparent power. Basis for calculation is the motor data
P201...P209.
P727
Mechanical power
(Mechanical power)
x
-99.99 ... 99.99 kW
Displays the actual calculated effective power of the motor.
P728
Actual mains voltage
(Actual mains voltage)
x
0 ... 1000 V
Displays the actual mains voltage at the motor starter input.
P732
Phase U current
(U phase current)
x
0.0 ... 999.9 A
Displays the actual U phase current.
NOTE:
This value can deviate somewhat from the value in P719, due to the measurement
procedure used, even with symmetrical output currents.
P733
Phase V current
(V phase current)
x
0.0 ... 999.9 A
Displays the actual V phase current.
NOTE:
This value can deviate somewhat from the value in P719, due to the measurement
procedure used, even with symmetrical output currents.
P734
Phase W current
(W phase current)
x
0.0 ... 999.9 A
Displays the actual W phase current.
NOTE:
This value can deviate from the value in P719, due to the measurement procedure
used, even with symmetrical output currents.
P740
[-01]
...
[-09]
Process data Bus In
(Process data Bus In)
S
0000 ... FFFF
(hex)
This parameter provides information about the actual control word (STW) and the setpoints
(SW1-3) that are transferred via the bus systems.
[-01 ] = Control word
Control word
[-02] = setpoint value 1
(not used)
[-03] = setpoint value 2
(not used)
[-04] = setpoint value 3
(not used)
Setpoint data from main setpoint
[-05] = Parameter data In 1
[-06] = Parameter data In 2
[-07] = Parameter data In 3
[-08] = Parameter data In 4
[-09] = Parameter data In 5
Data during parameter transfer: Order
label (AK), Parameter number (PNU),
Index (IND), Parameter value (PWE1/2)