4 displays – NORD Drivesystems BU0135 User Manual
Page 58
SK 105E…175E Motor Starter Manual
58
Pre-series version
BU 0135 GB-2713
4.4.4
Displays
The status of the starter in the PROFIBUS is indicated by the "BR" LED.
As soon as this LED lights up green, the starter is in cyclic mode. This means that the PLC has detected the
starter on the bus, has configured it and communicates with it. If the LED does not light, the reason could be
one of the following points:
· 24V supply voltage connected to the starter?
· PROFIBUS cable connected between the PLC and the starter? In
case of direct connection to the terminals, check for switched con-
nections of PBRA and PBRB
· If this is the last participant on the bus, is the termination resistor switched in?
· PLC switched on and configured with the correct GSD file (NORD0DA5.gsd)?
· Does the address which is configured in the PLC match the address which is set on the starter?
LED
Meaning
OFF
No cyclic process data communication active. See below for causes
ON
Normal operation, cyclic process data communication in operation