3 Display and control
BU 0135 GB-2713
Pre-series version
43
3.2 Overview of external control devices
All parameters can be easily accessed for reading or editing by means of an optional SimpleBox or Parame-
terBox. The changed parameter data can then be stored in the non-volatile flash memory.
In addition, up to 5 complete motor starter data sets can be saved in the ParameterBox and then recalled.
The connection between a SimpleBox or ParameterBox and the SK 1x5E is made by means of two RJ12-
RJ12 cables and an RS 232 / RS 485 converter (SK TIE4-RS485-RS232 Part No. 275274603).
Module
Description
Data
SimpleBox
Handheld
SK CSX-3H*
Used (exclusively) for commissioning,
parameterisation, configuration and control
of the motor starter. Storage of the
parameters is not possible.
Manual BU
4-digit, 7-segment LED display
IP20
RJ12-RJ12 cable
(for connection to the starter)
Part No. 275281013
ParameterBox
Handheld
SK PAR-3H*
Used for commissioning, parameterisation,
configuration and control of the starter and
its options (SK xU4-…). Storage of
parameters is possible.
Manual BU 0040
4 digit back-lit LCD display, keyboard
Saves up to 5 complete motor starter data sets
IP20
RJ12-RJ12 cable (for connection to the starter / option)
USB-Cable
(for connection to PC)
Part No. 275281014
* Also required
Converter
SK TIE4-RS485-
RS232
Connection extension for the conversion of
the RS485 signal of the parameterisation
units SK CSX-3H or SK PAR-3H to the
RS232 signal of the starter
Data sheet TI 275274603
IP20
RJ12-RJ12 cable (for connection to the starter / option)
Part No. 275274603
Installation of the control unit is performed as follows:
1. Remove the housing cover (see Section 2.4).
2. Connect the RJ12-RJ12 cable between the control unit and the
RS485 socket of the converter (SK TIE4-RS485-RS232) (see
the arrow in the adjacent illustration).
3. Connect the RJ12-RJ12 cable between the motor starter and
the RS232 socket of the converter (SK TIE4-RS485-RS232).
4. During normal operation after commissioning, it is essential to
replace the protective caps and pay attention to sealing.
5. As long as the housing cover is open, take care that no dirt or
moisture enters the device.