4 control terminals – NORD Drivesystems BU0135 User Manual
Page 67
5 Parameterisation
BU 0135 GB-2713
Pre-series version
67
5.1.4
Control terminals
Parameter
{ Factory setting }
Setting value / Description / Note
READ
RAM
READ /
FLASH
FLASH
P400
[-01]
…
[-04]
Fnct. Potentiometer
(Potentiometer function)
x
0 ... 6
{ [-01] = 1 }
Rated current of
motor
{ [-02] = 2, 5
}
Locking time
Acceleration time
{ [-03] = 3 }
Starting torque
{ [-04] = 4, 6
}
Ramp time
Deceleration time
Here the set functions for up to four potentiometers can be viewed. It is not possible to change
the setting.
0 = No function, the potentiometer is not used
1 = Rated motor current, value for P203 as long as P130=0
2 = Locking time, value for P570 as long as P130=0
3 = Starting torque, value for P210 as long as P130=0
4 = Ramp times, value for P102 and P103 as long as P130=0
5 = Acceleration time, value for P102 as long as P130=0
6 = deceleration time, value for P103 as long as P130=0
P420
[-01]
…
[-07]
Digital inputs
(digital input functions)
x
0 ... 9
{ [-01] = 1 } Digital
input 1
{ [-02] = 2 } Digital
input 2
{ [-03] = 8 }
Thermistor
{ [-04] = 3 }
Bus In Bit 0
{ [-05] = 4 }
Bus In Bit 1
{ [-06] = 7 }
Bus In Bit 2
{ [-07] = 9 }
Bus In Bit 3
Here the set functions for up to seven digital inputs can be viewed. It is possible to change the
setting if parameter P130=1 is set. Otherwise the value can only be views and is fixed.
0 = No function
1 = Enable right (only possible for digital input 1 and 2)
2 = Enable left (only possible for digital input 1 and 2)
3 = Enable right via bus (only possible for digital inputs 4 to 7)
4 = Enable left via bus (only possible for digital inputs 4 to 7)
5 = Block voltage
6 = Quick stop
7 = Error acknowledgement
8 = PTC resistor input
9 = Release the brake
P427
Emerg. stop
Error
(Emergency stop on error)
x
0 ... 1
{ 0}
In case of errors E2.0, E3.0, E5.1 and E6.1 there is the option that the drive is not switched off
immediately if the error occurs, but rather with devices with a soft start function, these are run
down the ramp as normal before switch-off.
0 = Disabled: Automatic quick stop following error is deactivated
1 = Activated: Automatic quick stop following error is activated
11
Acceleration time for type SK 115E and SK 155E devices (5) – Locking time for all other devices (2)
12
Deceleration time for type SK 115E and SK 155E devices (6) – Ramp time for all other devices (4)
13
The thermistor input cannot be re-programmed to another function.