ELECTRICAL DATA
TCF12R18L-13
TCF12R20L-13
Unit Data
Full Load Amps
(1)
A
497.4
506
Maximum Start Amps
A
287.4
296
Mains Supply
VAC
400V (±10%) 3PH 50Hz
Recommended Mains Fuse Size
A
560
560
Max Mains Incoming Cable Size (Direct to 3 Phase Mains Isolator)
mm²
2x 300mm² (Torque >20Nm)
Independent Permanent Supply Recommended Fuse Size
A
25
25
Independent Permanent Supply
VAC
230V 1PH 50Hz (±10%)
Max Permanent Incoming Cable Size (Direct to Control Panel Isolator)
mm²
6mm² / 8 AWG
Control Circuit
VAC
24 VAC & 230VAC (±10%)
Evaporator
Immersion Heater Rating
W
500 (2x 250)
500 (2x 250)
External Trace Heating
Available (fitted by others)
W
500
500
Condenser Fan - Per Fan (AC)
Quantity
18
20
Full Load Amps
A
4.3
4.3
Locked Rotor Amps
A
15
15
Motor Rating
kW
1.8
1.8
Condenser Fan - Per Fan (EC)
Quantity
18
20
Full Load Amps
A
3.9
3.9
Locked Rotor Amps
A
N/A
N/A
Motor Rating
kW
2.56
2.56
Condenser Fan - Per Fan (EC High Air Volume)
Quantity
18
20
Full Load Amps
A
4.8
4.8
Locked Rotor Amps
A
N/A
N/A
Motor Rating
kW
3.10
3.10
Compressor - Per Compressor
Nominal Run Amps
A
210
210
Quantity
2
2
Motor Rating
kW
129
129
Start Amps
A
2
2
Type Of Start
Electronic Soft Start
Technical Data
Electrical
TCF12R18L-13, TCF12R20L-13
(1) Based at full load Conditions and AC Standard Fans
Pump electrical data is avaliable from Airedale upon request.