Enabling pumps, Chillers turbochill™ air cooled and freecool, Ope ra tion – Airedale TurboChill FreeCool 200kW - 1830kW User Manual
Page 124

124
Chiller Technical Manual 7525355 V1.1.0_04_2013
O
pe
ra
tion
Chillers
TurboChill™ Air Cooled and FreeCool
Enabling Pumps
Pump Start-Up
Use the start-up guide for the general setting of the CUE, pump controller including the setting of the correct direction of
rotation.
The start-up guide will be started the first time when the CUE is connected to a supply voltage.
It can be restarted in the menu under GENERAL. Please note that in this case all previous settings will be erased.
On
Off
Alarm
OK
CUE
GRUNDFOS
+
-
On /
Off
Navigates from one menu to
another. When the menu is
changed, the display shown
will always be the top display
of the new menu.
Navigates up and down in
the individual menu.
+
-
Change value in the value field
OK
On /
Off
Makes the pump ready for operation.
Starts or stops the pump.
Saves changed values, resets alarms
and expands the value field.
On (green)
● The pump is running or has stopped by a stop function
● If flashing, the pump has been stopped by the user
(CUE menu), external start/stop or bus.
Off (orange)
The pump has been stopped with the on/off button.
Alarm (red)
Indicates an alarm or a warning.
Editing Buttons
Navigation Buttons
Indicator Lights
Running the pump alone for low ambient flow protection or during commissioning.
To run the pumps alone without operating the compressors, the following procedure is carried out:
1. Set the remote unit ON / OFF to the OFF position (Open Circuit).
2. Remote pump ON / OFF to ON position (Closed Circuit).
3. Turn the unit ON by display through the microprocessor.
The pumps on the chiller will start. Cooling will not be enabled until the remote unit ON / OFF is to the ON position.
This method is used to ensure that there is water flow through the chiller during periods of unit shut down.
To reinstate cooling the unit remote ON / OFF is to be Closed.