Chillers turbochill™ air cooled and freecool – Airedale TurboChill FreeCool 200kW - 1830kW User Manual
Page 34

34
Introduction
Chiller Technical Manual 7525355 V1.1.0_04_2013
Chillers
TurboChill™ Air Cooled and FreeCool
Rain Hood
A rain hood shall be fitted to the TurboChill chiller which will allow the customer, (maintenance / commissioning
personnel), to work on the control panel whatever the weather with a reduced risk of sensitive electrical components
getting wet.
Discharge Air Plenum - Condenser Fan
Factory fitted and constructed from galvanised sheet steel coated with epoxy baked powder paint, this plenum shall
direct discharge air vertically which reduces air re-circulation and provides a degree of acoustic reduction in the
horizontal plane.
Standard unit colour shall be Light Grey (RAL 7035).
The overall unit height when fitted with the standard discharge air plenum is 2785mm.
Extended Discharge Air Plenum - Condenser Fan
Site fitted and constructed from galvanised sheet steel coated with epoxy baked powder paint, this plenum shall direct
discharge air vertically as an aid to minimise air re-circulation and also offers a degree of acoustic reduction in the
horizontal plane; site fitted.
Standard unit colour shall be Light Grey (RAL 7035).
The overall unit height when fitted with the extended discharge air plenum is 3285mm.