Unit lifting, Lifting dimensions, Chillers turbochill™ air cooled and freecool – Airedale TurboChill FreeCool 200kW - 1830kW User Manual
Page 107: Installation data
107
Chiller Technical Manual 7525355 V1.1.0_04_2013
In
sta
lla
tio
n
Chillers
TurboChill™ Air Cooled and FreeCool
Installation Data
Unit Lifting
•
Employ lifting specialists
•
Local codes and regulations relating to the lifting of this type of equipment should be observed
•
Use the lifting eye bolts/lifting lugs provided
•
Attach lifting chains to each of the lifting eye bolts/lifting lugs provided; each chain and eye bolt must be capable
of lifting the whole chiller
•
Lifting hole / lug dimension: 40mm
•
Use the appropriate spreader bars/lifting slings with the holes/lugs provided
•
Lift the unit slowly and evenly
•
If the unit is dropped, it should immediately be checked for damage and reported to Airedale
CAUTION
Only use lifting points provided.
The unit should be lifted from the base and where possible, with all packing and protection in position. If any other type
of slinging is used, due care should be taken to ensure that the slings do not crush the casework or coil.
Lifting Dimensions
A
≥A
4 Point
Number
of Fans
A (mm)
4
1533
6
2332
8
3464
10
4077