Chillers turbochill™ air cooled and freecool, Te ch nic al, Fre ec oo l – Airedale TurboChill FreeCool 200kW - 1830kW User Manual
Page 75: Technical data
75
Chiller Technical Manual 7525355 V1.1.0_04_2013
Te
ch
nic
al
Chillers
TurboChill™ Air Cooled and FreeCool
Fre
eC
oo
l
36
37
38
ELECTRICAL DATA
TCF11R08L-08
TCF11R10L-10
TCF12R08S-09
Unit Data
Full Load Amps
(1)
A
244.4
253
304.4
Maximum Start Amps
A
2
2
169.4
Mains Supply
VAC
400V (±10%) 3PH 50Hz
Recommended Mains Fuse Size
A
315
315
315
Max Mains Incoming Cable Size (Direct to 3 Phase Mains Isolator)
mm²
2x 300mm² (Torque >20Nm)
Independent Permanent Supply Recommended Fuse Size
A
25
25
25
Independent Permanent Supply
VAC
230V 1PH 50Hz (±10%)
Max Permanent Incoming Cable Size (Direct to Control Panel Isolator)
mm²
6mm² / 8 AWG
Control Circuit
VAC
24 VAC & 230VAC (±10%)
Evaporator
Immersion Heater Rating
W
500 (2x 250)
500 (2x 250)
500 (2x 250)
External Trace Heating
Available (fitted by others)
W
500
500
500
Condenser Fan - Per Fan (AC)
Quantity
8
10
8
Full Load Amps
A
4.3
4.3
4.3
Locked Rotor Amps
A
15
15
15
Motor Rating
kW
1.8
1.8
1.8
Condenser Fan - Per Fan (EC)
Quantity
8
10
8
Full Load Amps
A
3.9
3.9
3.9
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
2.56
2.56
2.56
Condenser Fan - Per Fan (EC High Air Volume)
Quantity
8
10
8
Full Load Amps
A
4.8
4.8
4.8
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
3.10
3.10
3.10
Compressor - Per Compressor
Nominal Run Amps
A
210
210
135
Quantity
1
1
2
Motor Rating
kW
129
129
87
Start Amps
A
2
2
2
Type Of Start
Electronic Soft Start
Technical Data
Electrical
TCF11R08L-08, TCF11R10L-10, TCF12R08S-09
(1) Based at full load Conditions and AC Standard Fans
Pump electrical data is avaliable from Airedale upon request.