Positioning, Airflow & maintenance clearances, Positioning 114 airflow & maintenance clearances – Airedale TurboChill FreeCool 200kW - 1830kW User Manual
Page 114: Chillers turbochill™ air cooled and freecool

114
Chiller Technical Manual 7525355 V1.1.0_04_2013
In
st
alla
tio
n
Chillers
TurboChill™ Air Cooled and FreeCool
Installation Data
Positioning
The installation position should be selected with the following points in mind:
•
Position on a stable and even base, levelled to ensure that the compressor operates correctly
•
Levelling should be to +/- 5mm
•
Where vibration transmission to the building structure is possible, fit spring anti-vibration mounts and flexible
water connections
•
Observe airflow and maintenance clearances
•
Pipe work and electrical connections are readily accessible
•
Where multiple units are installed, due care should be taken to avoid the discharge air from each unit adversely
affecting other units in the vicinity
•
Within a side enclosed installation, the fan MUST be higher than the enclosing structure
•
Increase airflow and maintenance clearances for side-enclosed or multiple unit applications
•
Ensure there are no obstructions directly above the fans
•
Allow free space above the fans to prevent air recirculation
Airflow & Maintenance Clearances
Application
Distance from Overall Base Dimension
Single unit
1300mm
Side-enclosed or multiple units
2600mm