Chiller Technical Manual 7525355 V1.1.0_03_2013
D
esi
gn
Chillers
TurboChill™ Air Cooled and FreeCool
Capacity Data
For guidance, a number of units from 200 kW to 900 kW at nominal conditions and at both fan speeds have been pre-
selected and used throughout this manual for information only.
Please contact Airedale with your specific requirements and we will be pleased to provide you with an individually
tailored selection and technical detail.
Operating Limits
(For 100% Water) Standard Unit
Minimum ambient air DB
-20°C
Maximum ambient air DB at full load operation
35°C
Maximum ambient air DB at reduced load operation
40°C
Minimum supply water temperature
+5°C
Maximum return water temperature
+26°C*
Maximum supply water temperature
18°C
Minimum / maximum ΔT
4K / 8K
* With an 8K ∆T