KYORITSU 6305 Instruction Manual User Manual
Page 31

KEW6305
4.4
“Setting 02” Voltage rang
Selecting a measurement range so that the estimated inputs will be close to the full scale value is
recommended to obtain accurate results. Recommended range selections are: 150V range for rated
voltages between 100 - 120V, 300V range for 200 - 240V and 600V range for 400 – 440V.
Setting item
150V / 300V / 600V
Default value (or after system reset)
300V
1 Use the
Cursor
key on the selection screen, and select “Setting 02”.
2 Press the
ENTER
key to get the instrument into setting change mode.
3 Present setting (or default value: 300V) blinks. Select the appropriate voltage range with the
Cursor
key, and then press the
ENTER
key after making necessary change.
See also other documents in the category KYORITSU Tools:
- 1009 (13 pages)
- 1011 (12 pages)
- 1012 (12 pages)
- 1018 (1 page)
- 1030 (1 page)
- 1061 (58 pages)
- 1051 (40 pages)
- 1109S (36 pages)
- 1110 (1 page)
- 2000 (1 page)
- 2002PA (27 pages)
- 2007A (1 page)
- 2009R (33 pages)
- 2012R (2 pages)
- 2017 (1 page)
- 2031 (1 page)
- 2033 (9 pages)
- 2040 (2 pages)
- 2046R (2 pages)
- 2200 (3 pages)
- 2210R (1 page)
- 2300R (1 page)
- 2413F (24 pages)
- 2413R (24 pages)
- 2431 (2 pages)
- 2432 (1 page)
- 2433R (1 page)
- 2434 (10 pages)
- 2500 (1 page)
- 2608A (2 pages)
- 3005A (24 pages)
- 3021 (24 pages)
- 3121A (12 pages)
- 3126 (28 pages)
- 3127 (60 pages)
- 3128 (88 pages)
- 3131A (20 pages)
- 3132A (20 pages)
- 3161A (24 pages)
- 3321A (24 pages)
- 4105A (10 pages)
- 4106 (48 pages)
- 4116A (20 pages)
- 4140 (32 pages)
- 4200 (24 pages)