beautypg.com

1 demand measurement – KYORITSU 6305 Instruction Manual User Manual

Page 101

background image

KEW6305

8.4

8-1 Demand measurement

The following is an example of power management by monitoring the demand.

● Reducing the average power during a specific interval

Assume the interval to be 30mins.
In the figure below, the average power during Interval 1 is assumed to be 500kW and during Interval 2
is assumed to be 600kW.

(kW)

600kW

600kW

500kW 500kW

0

15 30 15

30(min.)


Now, assume that the average power during the first 15 min. (the inspection cycle) of Interval 2 is
600kW. The average power during Interval 2 can be maintained at 500kW (same as Interval 1) by
reducing the power of the last 15 min. to 400kW.

(kW)

600kW

500kW 500kW

400kW

0

15 30 15

30(min.)

If say, the average power during the first 15 min. is 1000kW then the average power during the
second 15min should be 0kW to maintain an average power of 500kW.

Average power

600kW

Interval 1

Interval 2

Average power

500kW

Interval 1

Interval 2

Average power

500kW

Average power

500kW